Z900 Zone
Planning Instructions..

Zone Type Definition Value
Zones
010203040506

Burglar
Loops
Entry Delay 1
Instant
Silent instant
Entry Delay 2
Interior
Non-Shuntable
Slow Response
Supervisory/TBL
= 0
= 1
= 7
= 8
= 16
= 32
= 64
= 128

Auxiliary "A" (Fire)
Shuntable
Slow Response
= 2
= 32
= 64

Auxiliary "B" (Police)
No Aux "B" alarm output
No Violation output on Z729
Shuntable
Slow Response
Supervisory/TBL
= 3
= 8
= 16
= 32
= 64
= 128

Auxiliary "C" (Emergency)
Shuntable
Slow Response
Supervisory/TBL
= 4
= 32
= 64
= 128

KeySwitch Momentary
Maintained Type
Shuntable
Supervisory/TBL
= 5
= 16
= 32
= 128

Communicator Report Only
Shuntable
Slow Response
Supervisory/TBL
= 6
= 32
= 64
= 128

Total Value for Selected Zone Type = (__)(__)(__)(__)(__)(__)

Function # for entering value total 414243444546

Default values are:
Zone 1= (41)= 64 (entry delay 1 (0) + slow response (64)
Zone 2= (42)= 72 (entry delay 2 (8) + slow response (64)
Zone 3= (43)= 81 (instant (1) + interior (16) + slow response (64)
Zone 4= (44)= 65 (instant (1) + slow response (64)
Zone 5= (45)= 65 (instant (1) + slow response (64)
Zone 6= (46)= 66 (fire (2) + slow response (64)